MCOM200M is GSM Based
Starter, the device works for 2 Phase/ 3Phase up to 80 Hp.it can be connect to
any type of Starter. Eg. DOL and Star delta etc.Through Mcom200M can operate
Pump from anywhere or Local.
Features
·
built-in 32-bit ARM Micro controller
·
built-in Watchdog
·
Current Range / HP: 3 – 99 Amps/1-80 Hp
·
built-in seven segment
display: Digital
Voltmeter 180 – 520 V and Digital Ammeter 3 – 99 Amp, GSM Network availability
in Percentage.
·
Push
button for Auto and Manual selection
·
Two
Mode operations: -Auto (online) and Manual (local)
Manual Mode: - Users can operate
pump through local ON/OFF push button with Protections.
Auto Mode:Users can operate pump
through Mobile (SMS/Call/Web and Mobile App)
·
Start
/ Stop / Monitor / Set your motor from any phone
·
Real
time IoT based data monitoring web and mobile app for pump status.
·
Talks
Online in Local Language
·
Four
Authorized users can be added
·
SMS
and online Realtime reports
·
Online
Parameter Settings by SMS and web /mobile App.
·
Call
Auto Lift and Auto Cut
·
Hour
Meter, Total Hour
·
MeterSite
Settable Four Digit Password with SIM Tracking
·
Missed
Call/SMSand web & Mobile app based ON / OFF pump operation.
·
Web
Based Android Application
·
Receive
Phone Call for Fault & Power Return (Call Back)
·
Select
Auto / Manual Mode by SMS, Web & Mobile app.
·
Real
timeVerbal Voltage & Current Information on web and Mobile APP.
·
Multi
Location with Fault and SMS Log in web /Android App.
·
IOT
Based Web Data Logging on Server
Protections:
·
Phase
Failure (Supply Side)
·
Phase
Failure (Motor Side)
·
Reverse
Phase (Supply Side)
·
Voltage
and Current Unbalance
·
Electronic
Overload (Site Settable)
·
Remote
Sensing Dryrun (Site Settable)
·
High
/ Low Voltage (Site Settable)
·
Extreme
High Current (Fixed at 50Amps.)
Timers:
·
Power
ON Timer for Auto Start (Site Settable)
·
Star
Delta Timer (Site Settable)
·
Dry
run Auto Start Timer OFF – 5 – 720 mins. (Site Settable)
·
Clock
Based 4 ON & 4 OFF Timers (MTC)
·
Motor
OFF Timer OFF – 5 – 720 mins. (Site Settable)
·
Repeat
Run Timer OFF – 5 – 999 mins. (Site Settable)
·
Time
Compensation Enable / Disable Facility
Specifications
1. System
Settings
• Input Voltage (AC) : 250 – 470 VAC, 50 Hz
• On voltage (Cold Start): 250
VAC
• Auto Off voltage: 200 VAC
2.
Protections / Setting Parameters
Pump Current Range : 3 – 99 Amp.
Parameter |
Setting Range |
Default setting |
Trip Time Delay |
Display |
LED |
Phase Failure |
Fixed |
Fixed |
4 sec ± 1 sec |
SPP |
YES |
Reverse Phase |
Fixed |
Fixed |
4 sec ± 1 sec |
SPP |
YES |
Voltage Unbalance |
Fixed |
Fixed |
4 sec ± 1 sec |
SPP |
YES |
Current Unbalance |
20% – 70% |
50% |
4 sec ± 1 sec |
CUB |
YES |
Overload |
20% – 60% |
> 140 % |
15 sec |
OL |
YES |
Dry run |
60% – 95% |
< 75 % |
15 sec |
DRN |
YES |
High voltage |
450 – 500 V |
480 V ± 2 V |
Fixed |
HIU |
YES |
Low voltage |
180 – 350 V |
250 V ± 2 V |
Fixed |
LOU |
YES |
Extremely
High Current |
Fixed |
50
Amps. |
3
sec |
EHC |
NO |
3.TimersSetting
Parameter |
Setting Range |
Default setting |
Display |
LED |
Power on Timer |
3 sec – 300 sec |
60 sec ± 3 sec |
PONT |
YES |
Star Delta Timer |
3 sec – 300 sec |
10 sec ± 2 sec |
OFF |
YES |
Motor ON Timer |
5 – 720 min |
OFF |
OFF |
YES |
Repeat Run Timer |
5 – 999 min |
OFF |
RRT |
YES |
Dryrun Auto Start Timer |
5 – 720 min |
OFF |
DRAT |
YES |
Clock Based 4 MTC Timer |
As per 24 Hours |
OFF |
OFF |
YES |
Cyclic Timer |
Clock 24 Hours |
OFF |
CYC |
YES |
4.
Monitoring Display
• Digital
Voltmeter : 180 – 520 V
• Digital
Ammeter : 3 – 99 Amp
5.Monitoring
Web and Mobile app:
·
Real
time monitoring for all parameters.
6.
Reset
• Resetting mode : Manual by OFF switch, SMS, WEB, Mobile
app.
7.
Output Relay Contact
• Relay
Mechanical life : 10 lac
operations
• Dielectric
Strength : 2.2 KV , 50 Hz for 1 min
8.
Enclosure & Mounting
• Enclosure
Material : MS powder coated Enclosure
• Mounting : Wall Mounting with 4 screw M4 × 15 mm
• Temperature : 5 to 60°C
• Humidity : Up to 90% RH
9.
Dimensions & Weight
• L × W × D (mm) : 250 x 160 x 74mm
• Power
Consumption : Less than 4 Watts
• Weights : 990 gms.
Applications
Industrial
Agriculture
Irrigation
Domestic
Connection
Diagram
INPUT 415 VOLT |
PUMP START |
PUMP STOP |
CT CONECTION (R Y B) |
THREE WIRE FOR THREE PHASE SUPPLY, RED FOR R
PHASE, YELLOW FOR Y PHASE, BLUE FOR B PHASE. |
TWO GREEN WIRE |
TWO BLACK WIRE |
TWO WIRE FOR R PHASE (Red and black), TWO WIRE FOR
YPHASE (Yellow and black), TWO WIRE FOR BPHASE (Blue and black). |